Tag Archive for: 800 V sidecar

Del bus 800 V ferroviario al rack de IAApplication Notes, Data Center

From the 800 V Railway Bus to the AI Rack: The Power Conversion Chain Premium Already Knows

Engineering Insight · GaN / HVDC

From the 800 V Railway Bus to the AI Rack: The Power Conversion Chain Premium Already Knows

How experience with 800 V traction converters applies to the 800 VDC sidecar architecture for AI data centres: GaN, the ALL2GaN programme and the EV supply chain.

The European ALL2GaN programme closed its thirty-six months of work in April 2026, at the same time as the AI data centre ecosystem was holding its largest annual gathering in Barcelona. The timing is telling: it marks the moment at which European gallium nitride and the high-voltage DC conversion architecture of the data centre converge on the same point of the industrial roadmap. This article reviews the data points presented at the OCP EMEA Summit 2026 that support this convergence with verifiable external evidence.

The convergence the summit confirmed

The convergence between the 800 V bus of railway traction and the 800 V bus of the AI data centre had until recently been a prospective thesis. The OCP EMEA Summit 2026 turned it into an established fact, documented by three independent industrial sources.

Schneider Electric set the limit of the 54 VDC bus at 400 kW/rack — the same threshold above which HVDC architecture becomes necessary, not optional. OmniOn Power quantified the difference: moving from the ORv3 chain (480 V → 54 V → 12 V → core, η 83.8 %) to the Next Gen 800 V chain (480 V → 800 V → 54 V → 12 V → core, η 85.8 %) saves 1.9 percentage points of efficiency — 2 MW for every 100 MW of installed DC capacity. Eaton displayed at the CCIB Innovation Village a physical prototype of the 800 V DC Side Car with a 33 kW ORV3 Power Shelf and scalable DC connectors at 63, 125 and 250 A.

The most significant data point, however, was not a number but a sentence. Schneider Electric, in its Day 2 plenary keynote, justified the 800 V sidecar with four arguments, the last of which was: leverages established EV supply chain. The EV supply chain — the same value chain in which Premium operates with its portfolio of converters for traction, e-mobility and railway auxiliaries — is the argument one of the world’s leading energy management manufacturers used to explain why the 800 V sidecar is the lowest-risk option in the short term.

“48–54 VDC rack power distribution and 480 VAC supply voltage approaches reach practical limits beyond ~400 kW/rack.”

— Schneider Electric, OCP EMEA Summit 2026, Barcelona, 30 April 2026

For a broader overview of the architecture, see The 800 VDC revolution: the energy engine behind AI.

ALL2GaN T6.2 Transport: programme context

The ALL2GaN programme — Affordable smart GaN IC solutions for greener applications — was launched in May 2023 in Villach and closed in April 2026. Coordinated by Infineon Technologies Austria AG, funded by the Chips Joint Undertaking (successor to KDT-JU) and framed within the European Chips Act and the Green Deal, it involved 45 industrial and research partners from twelve European countries.

Premium SA participates in the programme’s Transport cluster as a contributor to the development of compact power electronics building blocks for auxiliary applications. The UC3 use case from the official WP6 M36 deliverable defines the technical context: power converters for traction auxiliaries meeting the temperature, vibration, EMC and reliability requirements of the railway environment certified to EN 50155. This is exactly the design discipline profile the 800 V sidecar for data centres requires.

Why GaN is the sidecar technology

Gallium nitride is not merely an incremental improvement over silicon for DC/DC converters. It is the technology that makes possible the WBG DC/DC shelf stage of the Next Gen 800 V chain — the conversion from 800 V to 54 V at η 98.50 % in a high power density format.

GaN’s advantages over silicon in this context are threefold. First, the switching frequency can be five to ten times higher than conventional silicon, reducing the size of magnetic components and enabling power densities above 40–60 W/in³ on platforms with PCB-integrated planar magnetics. Second, switching losses are dramatically lower, with peak efficiencies above 97–98 % in real operation — not just catalogue conditions. Third, compared to SiC, GaN offers a complementary sweet spot in the medium-voltage, high-frequency band that is exactly the one dominating the WBG DC/DC shelf stage of the 800 V sidecar.

The contribution of the ALL2GaN programme is that these advantages now have a verified industrial value chain in Europe: from substrate to packaging, from reliability to application, production can be carried out entirely within the Union. This answers the industrial sovereignty question the sidecar architecture will face as regulated European hyperscalers demand supply chain traceability for their power components.

The EV supply chain as a bridge between worlds

The Schneider Electric phrase — leverages established EV supply chain — has an immediate practical implication for any power electronics manufacturer with a background in traction or e-mobility.

The components that make the 800 V sidecar possible — high-current DC connectors, high-voltage DC busbars, 4,000–5,000 A DC circuit breakers, copper cables with insulation for 800–1,000 V — are the same components the EV industry has standardised over the past decade. The technical qualifications, insulation tests, DC arc tests and earthing protocols developed for the electric vehicle are directly applicable to the data centre sidecar.

For Premium SA, which has operated for over 40 years in the railway and industrial power electronics supply chain for high-reliability applications, this has a direct technical reading: the company’s industrial track record is not just a credibility antecedent — it is the technical foundation that the sidecar market requires.

Key data points presented at OCP EMEA Summit 2026

Data point Technical implication
54 V bus limit: ~400 kW/rack (Schneider Electric) Defines the threshold above which HVDC distribution becomes necessary. A publicly verifiable data point.
Copper mass 200 kg → 13.5 kg per 1 MW rack (OmniOn Power) Quantifies the physical and material advantage of 800 V distribution.
Chain efficiency gain: +1.9 pp (ORv3 83.8 % → 800 V 85.8 %) (OmniOn Power) Concrete efficiency improvement across the full conversion chain, with public attribution.
“Leverages established EV supply chain” (Schneider Electric) Components, qualifications and test practices from traction and e-mobility carry over to the 800 V sidecar.
Physical 800 V DC Side Car prototype (Eaton) Confirms the architecture has moved from literature to product engineering.

Key takeaway: the convergence of the 800 V bus of railway traction with the 800 V bus of the AI data centre is no longer a thesis but an industry consensus, as the OCP EMEA Summit 2026 confirmed. Schneider Electric set out the case for the sidecar. Eaton showed a physical prototype. OmniOn Power quantified that every 100 MW of DC capacity installed at 800 V instead of 54 V saves 2 MW in losses — and that the copper mass per 1 MW rack drops from 200 to 13.5 kg.

Sources

  • ALL2GaN (Chips JU, formerly KDT-JU) — WP6 M36 public deliverable (UC3, T6.2 Transport).
  • Schneider Electric — keynote, OCP EMEA Summit 2026 (30 April 2026): “Next-generation AI rack densities”, “The sidecar is the immediate enabler.”
  • OmniOn Power — Philip Zuk keynote, OCP EMEA Summit 2026 (29 April 2026): ORv3 vs. 800 V chain and Osprey portfolio.
  • OCP Foundation — DCF Power Distribution LVDC v1.0 (29 April 2026).

Power designed for your application

Premium SA designs and manufactures industrial power converters in Barcelona for railway, data centre and electrification applications.

Contact the technical team

sidecarApplication Notes, Data Center

LIC, BBU and the 1–50 ms Window: Transient Management in the 800 V Sidecar

Application Note · Data Center

LIC, BBU and the 1–50 ms Window: Transient Management in the 800 V Sidecar

How Lithium Ion Capacitors, battery backup units and SCMI power capping deal with AI workload power transients in 800 VDC rack architectures.

The 800 V sidecar solves the problem of power distribution to the compute rack. But it does not solve the problem of the power transients that AI silicon workloads generate on millisecond timescales. That window — between 1 and 50 ms — is the territory of the Lithium Ion Capacitor (LIC) and the Battery Backup Unit (BBU), and it is also territory where the discipline of industrial power electronics has a direct and immediate application.

The 1–50 ms window: why it matters

Artificial intelligence workloads generate power transients that did not exist in the previous generation of data centres. When a GPU cluster initiates an intensive compute phase — the first token of an inference, the start of a training step — power demand can ramp in milliseconds from an idle value to the rack’s maximum power. That power step has two consequences.

The first is electrical: the facility rectifier and distribution system cannot respond fast enough. The bus voltage momentarily drops until the supply chain stabilises. If that voltage drop exceeds the silicon’s tolerance threshold — typically ±5% of nominal — the GPU controller activates the throttling mechanism, reducing clock frequency until the voltage recovers. The result is a direct degradation of compute performance.

The second consequence is mechanical and reliability-related: repeated load step and unload cycles accelerate ageing of decoupling capacitors, power modules and rack converters. In racks of 125–140 kW such as NVIDIA’s NVL72, the energy involved in those transients is sufficient to damage components dimensioned for steady-state operation if it is not actively managed.

The SCMI management framework: power capping and PID loop

The OCP EMEA Summit 2026, held in Barcelona in April 2026, added a new dimension to the transient problem: coordinated management from the Data Centre Manager (DCM) level. A joint session by Oracle, AMI and Arm presented Arm SCMI (System Control and Management Interface) as the standard protocol for the DCM to impose power policies at the silicon and power converter level.

The POWERCAP_CAP_SET and POWERCAP_CAP_GET power capping commands allow the DCM to set a consumption ceiling per power domain. Levels CPL0 to CPL3 define four degrees of restriction, from the sustained level (CPL0) to the critical level (CPL3). Concurrent Power Capping (CPC) enables simultaneous restrictions across multiple domains.

The interaction with the closed thermal loop is equally relevant. Without a closed loop coordinating cooling with silicon power demand, the only response to a thermal transient is processor throttling — a performance degradation. With the DCM’s PID loop acting on pumps, valves and CDU flow rate, the system can increase cooling before the silicon reaches its thermal limit, preserving compute performance.

LIC and BBU: the state of the art at rack scale

The reference solution for transient management in the AI rack is a two-stage temporal architecture. The Lithium Ion Capacitor (LIC) covers the ultra-short window of 1 to 50 ms — the energy needed to hold the rack bus while the supply chain responds to the load step. The Battery Backup Unit (BBU) covers the seconds-to-minutes window — the backup needed for an orderly shutdown or to ride through micro-outages.

The LIC is neither a supercapacitor nor a lithium-ion battery. It is a hybrid technology that combines the high specific power of the supercapacitor with an energy density intermediate between the supercapacitor and the battery. In the rack context, a LIC module at rack scale typically provides between 100 and 500 Wh of usable energy with a discharge power of 10–50 kW for the 1–50 ms window, in a format compatible with standard rack U-space. The cycle life of a LIC — typically above 100,000 cycles at 80% depth of discharge — is compatible with the daily cycle count of an AI rack in production.

Implications for the sidecar power converter

For the sidecar converter, the two-stage LIC + BBU architecture implies specific design requirements. The 800 V DC bus must support the connection of LIC and BBU modules without intermediate conversion — which requires that bus voltage tolerance and protection coordination are designed for bidirectional energy flows. The converter supervisor must expose telemetry at the granularity and latency the DCM’s PID loop needs: instantaneous output power, semiconductor temperature, transformer temperature and instantaneous efficiency, updated at intervals below 100 ms.

The converter must also respond to SCMI POWERCAP_CAP_SET/GET commands in times consistent with the control loop dynamics. This is a firmware requirement that today is not standardised in most industrial converters, and one that converter manufacturers will need to address.

Lessons from railway power electronics

The transient management problem in the AI rack is structurally similar to two problems Premium SA has addressed in the railway environment: the management of regenerative braking transients in traction auxiliaries, and the management of load disconnection transients in EN 50155-certified on-board systems. In both cases, the critical window is in the range of tens of milliseconds, the energy involved is in the range of hundreds of watt-hours at power levels of tens of kilowatts, and the reliability requirement is above 99.9% availability over a lifetime of ten to twenty years.

The engineering approach applied to railway traction — conservative derating, accelerated thermal cycling qualification, FMEA at component level — is the same approach that the 1–50 ms transient management problem in the AI rack demands.

References

  • Oracle, AMI, Arm — Systems Management session, OCP EMEA Summit 2026 (Barcelona, April 2026): Arm SCMI power capping architecture.
  • Open Compute Project Foundation — Data Center Facility: Low Voltage DC Power Distribution white paper v1.0 (approved April 2026).
  • NVIDIA — GB200 NVL72 rack power specification.
About Premium SA — Premium SA is a Barcelona-based designer and manufacturer of custom power converters for railway, energy, industrial, data centre and defence applications. Founded in 1981, the company brings over 40 years of experience in high-reliability power electronics.

Power designed for your application

Talk to our engineering team about power conversion for 800 VDC data centre architectures.